Using RTU Outlets J1 and J2 Simultaneously on Sun Fire 3800/4800/4810/6800 Racks and Sun Fire Cabinets May Cause System Power Outage |
|
| Category : | Availability |
| Release Phase : | Resolved |
| Product : | Sun Fire 3800 Server Sun Fire 4800 Server Sun Fire 4810 Server Sun Fire 6800 Server
|
| Bug Id : | 4855900
|
| Date of Resolved Release : | 06-MAY-2003
|
Impact
The Redundant Transfer Unit (RTU) in the Sun Fire 3800/4800/4810/6800 racks and Sun Fire cabinets support redundant power. The RTU has two outlets labeled J1 and J2, and all Sun Fire servers are shipped with J1 connected. Using RTU J1 and J2 simultaneously may cause a power overload condition, resulting in system power outage.
Contributing Factors
This issue can occur on the following platforms:
SPARC Platform
-
RTU Outlets J1 and J2 on Sun Fire 3800/4800/4810/6800 racks and Sun Fire cabinets.
Note: This issue occurs only if attempting to use RTU J1 and J2 simultaneously.
Symptoms
There are no predictable symptoms that would indicate the described issue.
Workaround
There is no workaround. The Sun Fire Cabinet Matrix document specifically states "Do not use J2". Please see the "Resolution" section below. See page A-4 of "Sun Fire 6800 System and Sun Fire Cabinet Rackmount Placement Matrix" at:
http://www.sun.com/products-n-solutions/hardware/docs/pdf/816-2062-17.pdf
Resolution
On Sun Fire 3800/4800/4810/6800 Racks and Sun Fire cabinets, do not use RTU outlets J1 and J2 simultaneously.