AC Sequencer Power Requirements
Operating Range
Nominal Voltage: 208, 220, 230, or 240 Volts AC
Operating Voltage: Single Phase 180-264 Volts AC
Frequency: 48-63 Hz
Current: 24 A maximum
AC Power Plug
The 230VAC power plug is a NEMA L6-30P. The 240VAC power
plug is a Blue, IEC 309, 2-Pole, 3-Wire, 32 Amp, with Ground at
the 6-hour position.
AC Power Cord
The 230VAC Power Sequencer uses a 12 AWG Type SJO flexible
cord rated at 25A when connected to utilization equipment with 2
current carrying conductors. Refer to Article 400-5 of the US
National Electrical Code.
NEMA L6-30R / ANSI C73.75 230 Volt Power Receptacle
30 Amp, 250V, 2-pole, 3-wire, Single Phase, Grounded

IEC 309 240 Volt Power Receptacle
32 Amp, 240V, 2-pole, 3-wire, Single Phase, Grounded

|